Carrier's ancillary network devices ensure optimum performance for BACnet MS/TP and other EIA-485 networks. These devices install easily and work together to amplify data signals and provide surge protection, bias and termination to any EIA-485 network.
Key Features & Benefits
The REP485 allows you to expand your overall network by repeating and amplifying network signals from one network segment to the next.
Specifications
Power
24VAC +/- 10%, 50-60z, 6 VA power consumption
Mounting
4" Snap Track
Terminals
Removable screw terminals
Ports
Net A and Net B are both EIA-485 (optically isolated)
Network Requirement
1 after every 31 controllers, after every 2000ft. (609.6m), or at each branch of a hybrid network
Network Wiring
22/24 AWG, single twisted shielded pair, low capacitance, CL2P wire
Operating Temperature
0° to 130°F (-17.8° to 54.4°C), 5-95% relative humidity, non-condensing
Listed by
UL-916 (PAZX), cUL-916 (PAZX7), CE EN50082-1997
Dimensions
4" (width) by 4" (height) by 2" (depth) / 102mm (width) by 102mm (height) by 51mm (depth)