i-Vu AppController

Item
OPN-APP
  • California Prop 65

OVERVIEW

General Purpose Controller

Programmable controller for utilizes a library of factory-engineered control programs for fan coils, unit ventilators, water source heat pumps and constant volume AHUs

The AppController continuously monitors and regulates equipment operation with reliability and precision. The AppController’s factory-engineered control programs provide optimum performance and energy efficiency for HVAC equipment such as fan coils, unit ventilators, water source heat pumps, and constant volume AHUs. It also features native BACnet communications and plug-and-play connectivity to the Carrier i-Vu Building Automation System.

FEATURES

Application Features

  • Library of factory-engineered control programs for fan coils, unit ventilators, water source heat pumps, and constant volume AHUs
  • Supports Snap graphical programming for creating customized control programs
  • Supports Carrier communicating room sensors, which allow for local setpoint adjustment and local overrides

Hardware Features

  • Battery-backed real time-clock keeps time in the event of power failure
  • Stand-alone control of up to 14 I/O points using proven algorithms
  • Native BACnet MS/TP communications

System Benefits

  • Fully plug-and-play with the Carrier i-Vu Building Automation System
  • Supports demand limiting for maximum energy savings

SPECIFICATIONS

BACNet SupportAdvanced application controller (B-AAC), as defined in BACNet 135-2001 Annex L
Communication PortsBACnet port: EIA-485 port for BACnet MS/TP communications (baud rates is DIP switch selectable)
Local Access port: For system start-up and troubleshooting (115.2 kbps)
Rnet port: For connecting Carrier communicating room sensors and Carrier's touchscreen user interface
Inputs6 inputs: Configurable for thermistor or dry contact. Inputs 1 and 2 are also configurable for 0-5 VDC. Inputs 7 and 8 are not used. AIs have 10 bit A/D resolution.
Outputs5 binary outputs: Relay contacts rated at 1A max @ 24 VAC/VDC, configured normally open.
3 analog outputs: Rated at 0-10VDC, 5mA max, with 8 bit D/A resolution using filtered PWM.
ProtectionIncoming power and network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events..
Real Time ClockBattery-backed real time clock keeps track of time in event of power failure
Battery10-year Lithium CR2032 battery provides a minimum of 10,000 hours of trend data & time retention during power outages.
Status IndicatorsLED status indicators for communications, run status, error, power, and all digital outputs.
Controller AddressingRotary DIP switches set BACnet MS/TP MAC address of controller.
Listed ByUL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE EN50082-1997
Environmental Operating RangeOperating: 0° to 140°F (-18° to 54°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Power Requirements24VAC +/- 10%, 50-60Hz
18VA power consumption
26VDC (25V min, 30V max
Single Class 2 source only, 100VA or less
DimensionsLength: 5-5/8” (14.31 cm)
Width: 5-1/8” (13 cm)
Depth: 2” (5.1 cm)
Weight: 0.44 lbs. (0.20 kg)

California residents please see Proposition 65

Safety Standards
California Prop 65 Yes
Hazardous Material No
Weights and Dimensions
Operating Weight (lbs) 1
Exterior Dimensions (D) (inches) 10.000000
Exterior Dimensions (W) (inches) 10.000000
Exterior Dimensions (H) (inches) 3.500000
Shipping Weight (lbs) 1.200000